Rinnai · Error code 11 · Checked November 2026
Rinnai error code 11: no ignition
Hot water is flowing and the heater tried to light, but the burner never caught. Most of the time it’s the gas supply.
Smell gas? Don’t touch any switch or try to reset anything. Leave the house, then call 911 or your gas company from outside. In Southern California that’s SoCalGas, 1-800-427-2200.
From Dan and Dave at Dan's Plumbing, a family plumbing shop in Westlake Village, California. Everything below comes from Rinnai’s own documents, cited line by line.
What it means
What Rinnai says code 11 means
“11 No Ignition (Heater Not Turning On)”— Tankless Water Heater (Residential) Installation and Operation Manual — RU199/RU180/RU160/RU130 i/e, page 73
Rinnai calls code 11 “no ignition.” Hot water is flowing and the heater tried to light, but the burner never caught. It means the same thing on every Rinnai tankless, from the newest SENSEI models to the older R-series and V-series.
The usual reason is gas: a valve that’s off, an empty propane tank, or gas pressure that drops when other appliances run. Rinnai’s troubleshooting guide also points to the igniter, the flame rod, the vent and, on condensing models, a blocked condensate line.
Model differences. SENSEI: ignition retries increased from 3 to 18 before Code 11 by a software update (TB-166). RH180 is in the guide’s Non-SENSEI steps (e.g., MSA/MSB not used on RH-180).
On other Rinnai models, 11 means something else:
- EH5L T5L failureThe lower tank water temperature sensor failed. On: REHP heat pump water heater (tank).
Why it happens
Likely causes of Rinnai code 11
- Gas off at the heater, meter or propane tank; empty propane tank; air in gas lines after install. (Diagnostic codes guide (2024), p. 16)
- Inlet gas pressure too low with all appliances running, undersized gas line/meter/regulator, or wrong gas type/parameter. (Diagnostic codes guide (2024), p. 16)
- Igniter not sparking, loose or dirty igniter/flame rod, wrong electrode gap (3.5 mm on SENSEI/RX/CX). (Diagnostic codes guide (2024), p. 16)
- Venting faults causing recirculated exhaust; blocked condensate line (SENSEI). (Diagnostic codes guide (2024), p. 17)
- Gas valve with debris or condensate inside; wet wiring; MSA/MSB staging fault. (Diagnostic codes guide (2024), p. 17)
- SENSEI software update raised ignition tries from 3 to 18 before showing Code 11. (Bulletin TB-166, p. 1)
What to do
Safe checks first. Then call a pro.
Safe checks you can do
What a technician checks, and why
- Verify all gas valves open, purge air, check inlet pressure against the rating plate with all gas appliances on high fire; check gas type and Parameter 10 (A = natural gas, B = propane).Gas pressure, gas type and gas-line work need a qualified gas technician. (Diagnostic codes guide (2024), p. 16)
- Spark-test the igniter with insulated pliers; check igniter voltage at the PC board; set electrode gap to 0.138 in. (3.5 mm).Live electrical testing inside the unit; Rinnai says only trained and qualified professionals should do it. (Diagnostic codes guide (2024), p. 16)
- Remove and clean igniter and flame rod; replace the gasket.Opens the burner/combustion chamber or gas valve. (Diagnostic codes guide (2024), p. 17)
- Check venting, equivalent length, altitude Parameter 02, two-stage regulator lock-up (max 10 in. w.c. natural gas / 13.5 in. propane), wet harnesses.Vent system changes and vent-length/DIP settings are installer work. (Diagnostic codes guide (2024), p. 17)
- Measure gas valve solenoid (SENSEI connector D pins 27–29: 18–22 ohms or 11–13 VDC); replace gas valve or PC board.Live electrical testing inside the unit; Rinnai says only trained and qualified professionals should do it. (Diagnostic codes guide (2024), p. 17)
- Non-SENSEI: remove burner manifold and burners, clean orifices and fins, reseat burner cassettes, check conversion orifice/O-ring.Opens the burner/combustion chamber or gas valve. (Diagnostic codes guide (2024), p. 19)
Please don’t
- Don’t open the burner, the gas valve or the sealed combustion chamber.
- Don’t keep resetting a code that keeps coming back. A code that returns means the cause is still there.
- Don’t bypass or unplug a safety sensor to get hot water back.
- Don’t cover, tape or move the vent or the air intake.
Heater getting old, or the same code keeps coming back? Repair or replace? Three taps and Dan’s answer → Or see what a water heater repair usually involves.
Common questions
Rinnai code 11 questions
Can I fix Rinnai code 11 myself?
Sometimes. Rinnai’s manuals list three owner checks: the gas is on at the heater, the meter or the propane tank; a propane tank isn’t empty; and, on condensing models, the condensate line isn’t blocked. Everything after that, like gas pressure, the igniter and the gas valve, is for a trained technician.
Why does my Rinnai show code 11 after an install or gas work?
Rinnai’s guide lists air in the gas line after an install as one cause, which a technician purges. Gas that was shut off at the heater or the meter and not turned back on is another.
Is Rinnai code 11 the same as code 12?
No. 11 means the burner never lit. 12 means it lit, then the flame went out or the heater couldn’t sense it.
Where this comes from
Sources
Taken from Rinnai’s own documents, checked November 13, 2026. Page numbers are the printed page. Where models differ, we say which model each part applies to.
- Tankless Water Heater (Residential) Installation and Operation Manual — RU199/RU180/RU160/RU130 i/e Rinnai America Corporation · 100000467 · (07) · Models: RU199i, RU180i, RU160i, RU130i, RU199e, RU180e, RU160e, RU130e
- Troubleshooting Tankless Water Heater Diagnostic Codes Rinnai America Corporation · 100000652 · file '100000652-Troubleshooting TWH Diagnostic Codes (3).pdf', PDF dated 2024-05-08; byte-identical to the library’s 'TWH Troubleshooting Technical Data Sheet' · Models: RU/RUR/RSC/CU SENSEI, RX/RXP/CX/CXP SENSEI RX/CX, RE/REP (VE), V53e/V53De/V65/V75/V94/V94X (VC Value), RL75/RL94/RLX94 (VC Luxury, VB), R50LS/R63LS/R75LS/R94LS/R98LS (VA), RC80/RC98 (KA), RU80/RU90/RU98, RUC80/90/98, C199 (KB/KBD), RUR98 (KBP), RUCS65/75, RUS65/75 (KCM), RH180 (HTT)
- Technical Bulletin 166 — Updates to PC Board Ignition Sequence Rinnai America Corporation · TB-166 · not printed · Models: SENSEI series, I-Series boilers